10.3.6.4.7 Server Disconnected Alert
The Server Disconnected Alert can be used to raise an alert when the connection
to N2KServer is lost due to network problems. As with the On and Off alerts, the
Set Delay and Clear Delay values are used to prevent spurious triggering.
Note that the Server Disconnected Alert will have some limitation as to the
Actions possible when the Alert is triggered. Because the connection to the
server has been lost, it will not be possible to display this alert on other N2KView
displays, or on DSM250 Displays. It will also not be possible to sound an
annunciator. It will be possible to send an email message if the computers
Ethernet connection is still available.
10.3.6.4.7.1 Trigger Configuration
Figure 94Trigger Configuration Editor - Tripped Alert
Accept Re-trigger PeriodWhen you accept an alert, it will change to the
“Accepted” state, and annunciators that are sounding for that alert will stop
sounding. If the condition which caused the alert remains true after the amount of
time in this field, the alert will return to the “Active” state, and annunciators will
begin sounding again for that alert.
If a value of 0:00 is entered, then the alert will never re-trigger.
Set DelayIf the switch being monitored is in the Trippedstate for the amount
of time specified in this field, the alert will become active.
Clear Delay If the switch being monitored is in a state other than “Tripped” for
the amount of time specified in this field, the alert will become inactive.
Revision 4.0.2 Page 265