13.6 Configuration
Configuration of Load Shedding is done in the Load Shedding Dialog; this is
accessed through the Load Shedding button in the Commands & Settings
Dialog.
Figure 109 – Load Shedding Dialog
13.6.1 General
Each Load Shedding Group is enabled / disabled using the Load Group
Enabled check box at the top left.
The Delay Between Sheds determines how often the Load Shedding Algorithm
runs. If this figure is too small, then the result of making a shed will not have
enough time to be measured by the ACM100 and reported back, and additional
loads will be shed unnecessarily. The system will become too responsive.
The currents reported by the Sources will be averaged over this period.
NOTE: Changes in the Load Shedding Dialog do NOT take effect until either the
Apply or Save button is pressed. Save will apply the changes and exit the
dialog. Cancel will exit the dialog without making any changes.