Due to the variety of links between the sources and the loads, N2KView may
switch off loads that are not connected to the overloaded source. This is the
safest way to ensure that all the sources are protected under all conditions,
without reprogramming the system each time the Power Distribution is changed.
The estimated Current Draw for each load must be programmed into N2KView
in the Load Shedding Dialog.
Only Loads controlled by the Moritz AC box, Moritz DC box, or Maretron’s
DCR100 are candidates for load shedding. The Moritz DC box and DCR100
would need to switch an AC load indirectly through a relay.
13.3 Startup
On startup, Load Shedding will always be disabled. To enable Load Shedding,
open the Commands & Settings Tab, and then press the Load Shedding
button. Click on the Load Shedding Enabled box and press Apply or Save.
13.4 Shedding Loads
If enabled, N2KView will start shedding loads (switching off the breakers) in order
when the current reported by any of the sources meet or exceed the Load
Shedding Current configured by the user for that source. The current is
averaged over the Delay Between Sheds period specified in the Load
Shedding Dialog.
In the case of a multi-phase source, the current reported will be the average of
the maximum currents reported by each phase. If individual phase currents are
not reported, then the average phase current will be used.
Breakers that are Locked will not be considered for Load Shedding.
Sources that do not report current will not be protected for Load Shedding.
Sources that do have a Load Shedding Current, or whose Load Shedding
Current has been set to zero will not be considered for Load Shedding. This is
the way to indicate to N2KView that a source is not being used.
13.5 Restoring Loads
If enabled, shed loads will be restored in reverse order when N2KView calculates
that adding the load back will not cause the current for each source to rise above
90% of the Load Shedding Current for that source. The assumption that the
current drawn by the load to be restored may increase the current required by
Revision 4.0.2 Page 351